TBS toxic gas detector

● Sewage and sewage treatment

Pump room, water collecting well, grille well, chlorination room, etc.


TBS toxic and combustible gas detector uses high-performance electrochemical sensors. Sensor elements of different gases can be used to detect a variety of different toxic and harmful gases. At the same time, the measured harmful gas concentration value can be converted into a 4-20 mA standard signal output. TBS The single-point wall-mounted gas alarm is mainly used for gas detection and alarm in non-explosion-proof occasions on industrial sites. It is equipped with one AC220V and one passive switching control signal output, which can control exhaust fans and other equipment.


Detection principle: catalytic combustion (combustible gas);

Electrochemical type (toxic gas / oxygen)

Sampling method: Natural diffusion

Debugging method: infrared remote control

Range: H2S: 0 ~ 100μmol / mol;

Cl2: 0 ~ 20μmol / mol

CH 4: 0 ~ 100% LEL;

CO: 0 ~ 1000μmol / mol

NH 3: 0 ~ 100μmol / mol

Accuracy: ± 5% FS

Environmental conditions: Temperature: -40 ° C to 70 ° C (combustible) -20 ° C to 50 ° C (poison gas / oxygen) Humidity: ≤ 95% RH

Explosion protection method: Flameproof

Explosion-proof grade: ExdIICT6

Protection level: IP55

Working power: DC24V ± 25%

Output signal: current: 4 ~ 20mA switch value: 2

Capacity: 0.5A / DC24V RS-485 bus

Use cable: ≥ 1.5mm2 × 3 shielded cable, the outer diameter of the cable must be between 6mm ~ 9mm

Transmission distance: ≤ 1000m

Machine weight: ≤ 2000g

Pressure limit: 86kPa ~ 106kPa

Installation thread: G3 / 4 (inner tube thread)

Dimensions: 210 × 200 × 105mm